To calculate the recommended pulling tension, the following formula includes the “rolling efficiency” of the stringing sheaves:

FORMULA

Pull Tension Calculation

The maximum pulling tension applied to the conductor should not exceed ten percent (10%) of the rated strength of the conductor, as recommended by IEEE Standard 524. For example, Drake ACSR has a rated strength of 31,500 lb. (140 kN), therefore the pulling tension should not exceed 3,150 lb. (14 kN) during the installation of the conductor. The formula above assumes a level pull. Pulls which include angles, elevation changes, tighter sag values and having to clear high obstacles will increase the pulling force required.

Fill out the fields below and then click “Calculate.”